Memory areas Section 3-2
60
3-2 Memory areas
Data exchange memory areas
The PLC CPU uses the following memory areas for data exchange with the
CJ1W-MCH72:
EM (Expanded Memory)
CIO (Common I/O memory)
DM (Data Memory)
WR memory
HR memory
The CJ1W-MCH72 uses the following memory areas to exchange data with
the PLC CPU:
VR memory
IN array (for digital inputs)
OP array (for digital outputs)
AIN array (for analogue inputs)
AOUT array (for analogue outputs)
Axis Status array (see section 3-3-2-1)
The mapping of memory areas for cyclic data exchange in the PLC CPU to
memory areas in the CJ1W-MCH72 can be freely configured. This can be
done in the PLC program or in the CJ1W-MCH72. It is recommended to
configure the memory mapping either in the startup program of the PLC or in
the startup program of the CJ1W-MCH72.
The memory mapping is not stored permanently and will be lost after a restart
of the CJ1W-MCH72 or a power cycle of the PLC system.
It is possible to configure the mapping of memory areas both in the PLC
program and in the CJ1W-MCH72. This is not practical, because the last
configuration overwrites the first.
CJ1W-MCH72
PLC CPU
IN
Digital and analogue
inputs and outputs
OP
AIN
AOUT
VREM
CIO
DM
HR
WR
Note Data exchange with the Table memory of the CJ1W-MCH72 is not possible. However,
with the FINS Write command you can write the Table memory of the CJ1W-MCH72.