System-10-P1 Manual 09/15 - 0656-11 / 18320 Page 24
3.3.4 Isolated Analog Output(s) (Optional):
The System-10 can be congured to provide up to four isolated analog outputs of the
following ve parameters: supply temperature, return temperature, ow rate, BTU rate and
delta temperature. The output type, 4-20 mA, 0-10 VDC or 5 VDC is eld congurable. The
selected outputs and associated scaling are congured at the factory. See the calibration sheet
or label, located on the inside cover, for analog output conguration information.
Please Note: If System-10 is ordered with a ow meter capable of producing an analog
output, ow rate analog output will be available at Terminal T4 from ow meter.