EasyManua.ls Logo

Openreach ONT - Ducting to the building; Ducting general principles

Openreach ONT
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Openreach: Developer Guide
Ducting to the building
Duct to the premises/building must be laid at
a minimum depth of 350mm and be as straight
as possible.
The latest information on the positioning
of utilities, mains and plant can be
obtained from the National Joint Utilities
Group: www.njug.org.uk
Please note
Ducting general principles
All runs shall be laid as straight as possible.
If needed, you can carefully bend the
ducts or use pre-formed bends supplied by
Openreach.
There shall be no more than one pre-formed
90° bend in any single run of duct.
Pre-formed 90° bends shall not be installed in
any duct linking two joint boxes.
Footpath or service strip ducting must be laid
at 350mm depth of cover.
All space alongside the duct must be
backlled with granular ll to a minimum
thickness of 75mm.
For all Single Dwelling Units (SDU) duct
must be terminated on the external surface
of the property.
The duct termination point shall be in a
location that will allow unrestricted access for
any future maintenance activity.
All ducts must be provided with a draw rope
after installation, unless it’s agreed locally to
substitute the draw rope with a cable.
Please notify your FBC when the duct has
been laid and is ready for inspection.
Commercial unit ducting
90mm duct can be laid either externally or
internally to the building, with 45 degree
angled bend.
If internally then the duct should be sealed
once cabling is complete – the FBC will
provide this as a stores item.
The termination point on a large
commercial unit within a commercial only
site should be located within 10m of the
entry point.
Duct laying

Table of Contents