6000 Series Digital Gas Monitor/Controller
Important Information !
This manual provides information required to install, operate and
maintain the series 6000 gas monitoring system. Read and study
before attempting to install or operate monitors. Installation
and operation not in accordance with this manual can result in a
hazardous situation or harm. Relay connections may be used to
control 120 Vac equipment. Ensure power is disconnected from
relays before attempting to service this unit.
1.0 General Description
Series 6000 gas monitors provide air quality monitoring for
commercial properties. Close monitoring of indoor air-born
pollutants and automatic fresh air controls improve the health and
well being of occupants and, also minimize excess ventilation,
reducing both energy costs and maintenance costs. The key to
maintaining this balance is a high level of precision coupled with a
robust design suited to tough commercial applications.
Each 6000 monitor can measure one or two gases and control
ventilation directly. They communicate with each other (up to 32)
via the chain network, so some monitors activate the ventilation
and others send the commands. The monitors are easily assigned
to groups on site for ventilation zoning on the same network. This
reduces control wiring signicantly.
The use of this peer-to-peer CAN network eliminates the need for a
costly controller on smaller projects. For the larger ones, a 6000-B
controller or addressable relay units can be added where starters
are centralized in the mechanical room. The monitors can also be
tied into a BACnet building automation system by simply connecting
an MS/TP cable to any monitor or 6000 controller on the CAN
network. The gas readings from all the monitors will display on the
BMS and the BMS can over-ride output relays on the monitor it is
connected to.