EasyManua.ls Logo

OPTI-UPS DS3000I - Page 12

Default Icon
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specification and performance
8 DS-I 1-3k UPS User Manual
Battery
Voltage
36VDC
72VDC
72VDC
Current
31A max
30A max
35A max
Output
Voltage
110V/115V/120V/127Vac120V Default
Current
6
.
7A
12
.
5A
16
.
7A
Dimension
(W*D*H) mm
144*353*222
190*374*336
190*374*336
Weight (kg)
12
22
22
2. Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
DS1000/2000/3000I
Single-phase
40-70Hz
>0.98(Full load)
3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0C-40C
<95%
<1000m
-20C-70C
NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be de-rated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
De-rating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Crest ratio
1%
0.9 lag
0.5% of
normal
THD<1%@Fu
ll Linear Load
THD<6%@Fu
ll nonlinear
load
130% load: transfers to
Bypass mode after 1
minutes
150% load: transfers to
Bypass mode after 0.5
minute
3:1
maximum

Related product manuals