17
Settings (Setup)
In this menu you can change certain settings, adjust the heating, temperature protection, auto
restart and hysteresis setting.
Press and hold theSbutton for longer than 6 seconds to access the settings menu. A capital letter
D appears on the screen followed by a number from 01 to 29. Press theSkey again briefly
pressing repeatedly run through the different settings.
The first setting is D: 01 second D: 02, etc.
To change a setting, you do so with the ▲ or ▼ button. To confirm this
press the ON / OFF key. If you want to change anything and exit the menu, press
press the R key.
The settings range from D 01 to D 32.
If you want to reset to factory settings press theMbutton while you are in the settings menu. All
settings are now defaulted back to factory settings. Confirm by pressing the on / off button.
D: 01 Heaters on / off
There are three heating elements in the OptiClimate. There are 1-phase systems in all three
connected to the first phase and at a 3 phase distributed over the 3 stages.
In the Settings menu, each of these elements can be turned on and also disabled. They can also all
be shut off when, for example, central heating is on.
Setting:
D: 1 = 3 means all three elements will heat
D: 1 = 2 means two elements will heat
D: 1 = 1 means the first element will heat
D: 1 = 0 means all the elements are off
D: 02 Temperature protection
If the room temperature is above 35 ° C, the unit via the terminals 15 and 16 will turn off the heat
source to the terminal strip. By setting D: 02 you may change the cut out to act between 30 ° C and
40 ° C. If the temperature drops below the set temperature, the cooling mode will disable security
again.
The security has no influence on the operation of the OptiClimate. However, there will be an error
message given, ie E: 15. (See also the error code list)
D: 03 Auto restart after power failure
If the voltage is interrupted when the unit is turned on, the voltage will return the unit to default
setting to allow it turn back on safely.
If after a power failure you want the unit to remain off; or when it is assumed an interruption has
occurred by external interference, connect the D setting: change to D 03.
Setting:
D: 03 = 0 means auto restart is off.
D: 03 = 1 means auto restart is on.
This is the default setting. There will always be an error code displayed when a power failure has
occurred, i.e. code 14. See also error code list.