Locking Screws Secure Shelf Rails to Rear Mounting Brackets
Legend Description
1 CPU 0
2 CPU 1
3 Towards the front of the CMOD
Locking Screws Secure Shelf Rails to Rear Mounting
Brackets
A pair of locking screws (provided) secure the shelf rails to the rear mounting brackets. These
screws prevent the mounting brackets from being accidentally disengaged, which could cause
the server to fall out of the rack.
How to Install the Locking Screws
Before You Begin
Install the server in the rack, as described in Installing the Server in a Rack Using the Universal
Rack Mounting Kit in Sun Fire X4800 Server Installation Guide.
1.
From the rear of the server, insert the screw (1) through the rack (2) and the rear
mounting bracket (3) so that it protrudes from the mounting bracket just above
the flange on the shelf rail (5).
For a round hole (tapped) rack, use either an M6 x 12 or a 10–32 x 7/16 screw.
For a square hole (untapped) rack (shown below), use an M6 cage nut (4) and an M6 x 16
screw.
The following figure shows the details for a square-hole (untapped) rack.