75
Charger connected to the vehicle
and a time programming but it
does not charge
If the time programming indicator is on
( ), swipe the RFID card to activate
the time programming.
If the time programming indicator is
off, the vehicle does not support
external time programming. Program
the time interval in the vehicle itself,
and eliminate the time programming
of the charger.
The protections of the installation
are triggered
If the charge modulation indicator is
off, the TMC100 is not properly
connected: Check connection to the
terminals, direction of current and
that the TMC100 securely fitted and
clamped in position as indicated in
the Load Modulator section.
If the charge modulation indicator is
on ( ), the adjusted power does
not match incoming power supply.
After manual deactivation or with
RFID card the charge does not
stop.
Disconnect the charger from the
vehicle.
If it has been activated with an RFID
card, the same card must be used to
deactivate.
If the problem persists, release and
disconnect the cable.
The charger could not connect to
a WiFi network
If the Wi-Fi indicator ( ) is in
flashing blue and does not pass to
solid blue, the charger has not been
correctly configured or the correct
password has not been entered.
If the Wi-Fi indicator is in solid blue it
is connected to a Wi-Fi network
without internet connection or the
security of the network is blocking it.
Charge complete, but cable and
vehicle remain locked with solid
green status bar.
Preform reset:
Reset the protected device, restart
the charger to be allowed to remove
the cable from the charger socket.
Exceeding maximum power
The modulator hasn't worked.
Check the configuration according to
the incoming power supply.