OSAKA – USER MANUAL – F 500 / F 500-RS – V.1 – Page 1
48
r.HC
Output operating mode:
H= Heating
C= Cooling
nr = Neutral Zone
HC =Neutral Zone with
ind. Set point
C3 = Cooling with 3 aut.
switch modes
H / C / nr / HC /
C3
C
49
r.tC
Lengh of “turbo” cycle
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
oF
]Fn
F. parameters relative to evaporator fans control
50
F.tn
Fan time activation
with ot output
(compressor) off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
5.00
51
F.tF
Fan time deactivation
with ot output
(compressor) off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
52
F.FL
High temperature fan
deactivation
- 99.9 ÷ 999
°C/°F
10.0
53
F.LF
Low temperature fan
deactivation
- 99.9 ÷ 999
°C/°F
-99.9
54
F.dF
Differential fan control
0.0 ÷ 30.0
°C/°F
1.0
55
F.FE
Fan status during
defrost
oF - on
oF
56
F.Fd
Fan delay after defrost
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
]Pr
P. parameters relative to compressor protection
and power on delay
57
P.P1
Output “ot” delay at
switch on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
58
P.P2
Output “ot” delay after
switch off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
59
P.P3
Output “ot” delay
between switching-on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
60
P.od
Delay outputs at power
on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
]AL
A. - parameters relative to alarms
61
A.y1
Temperature alarms 1
Type:
1 =Pr1 absolute with
label (H - L)
2 =Pr1 Relative with
label (H - L)
3 = “Au” absolute with
label (H - L)
4 =“Au” Relative with
label (H - L)
5 = “cd” absolute with
label (H - L)
6 = Pr1 absolute
without label
7 = Pr1 relative without
label
8 = “Au” absolute
without label
9 = “Au” relative
without label
10 = “cd” absolute
without label
1 / 2 / 3 / 4 / 5 /
6 / 7 / 8 / 9 / 10
1
62
A.H1
High temperature
Alarm 1 threshold
oF / -99.9 ÷
999 °C/°F
oF
63
A.L1
Low temperature
Alarm 1 threshold
oF / -99.9 ÷
999 °C/°F
oF
64
A.d1
Alarms A.H1 and A.L1
Hysteresis)
0.0 ÷ 30.0
°C/°F
1.0
65
A.t1
Alarms A.H1 and A.L1
delay
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
66
A.P1
Temperature Alarms 1
delay at power on
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
2.00
67
A.A1
Alarms H1 e L1 actions
0 = no actions
1 = activate alarm
outputs
2 = disable control
outputs (ot e HE) but
not activate alarm
outputs
3 = disable control
outputs (ot e HE) and
activate alarm outputs
0 / 1 / 2 / 3
1
68
A.y2
Temperature alarms 2
Type: see “A.y1”
1 / 2 / 3 / 4 / 5 /
6 / 7 / 8 / 9 / 10
3
69
A.H2
High temperature
Alarm 2 threshold
oF / -99.9 ÷
999 °C/°F
oF
70
A.L2
Low temperature
Alarm 2 threshold
oF / -99.9 ÷
999 °C/°F
oF
71
A.d2
Alarms A.H2 and A.L2
Hysteresis)
0.0 ÷ 30.0
°C/°F
1.0
72
A.t2
Alarms A.H2 and A.L2
delay
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
73
A.P2
Temperature Alarms 2
delay at power on
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
2.00
74
A.A2
Alarms H2 e L2 actions
0 = no actions
1 = activate alarm
outputs
2 = disable control
outputs (ot e HE) but
not activate alarm
outputs
3 = disable control
outputs (ot e HE) and
activate alarm outputs
0 / 1 / 2 / 3
1
75
A.dA
Temperature Alarms 1
delay after defrost, and
unlock display delay
after defrost
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
1.00
76
A.oA
Alarm delay with door
open
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
3.00
77
A.r1
(#)
A.H1 and A.L1 delay to
be recorded as an
HACCP alarm
(se =oF gli allarmi non
sono mai registrati
come HACCP)
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
78
A.r2
(#)
A.H2 and A.L2 delay to
be recorded as an
HACCP alarm
( =oF HACCP rec.
disable)
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF