HYDROFIT Owner’s Information Manual
WARNING: The use and ownership of this work is defined in the legend upon the front page hereof.
Card Reader Lockdown
When this feature is enabled, the car responds only to hall calls from a card reader.
When Card Reader in Hall security is activated, the Card Reader Lockdown feature
parks the car at a specified landing and takes it out of service, removing it from
group operation. If the car is set to park with its doors closed, the car moves to the
specified landing, opens its front doors for the maximum hall door time then closes
its doors and takes the elevator out of service.
Group Floor Cutoff Service
Group Floor Cutoff Service allows selected landings or calls to be secured for an
entire elevator group. A keyswitch activates the feature. Any landings secured are
still accessible during Firefighters’ Service Phase II operation.
Car Call Cut-Off (Selected Landings)
Car Call Cut-Off operates from a keyswitch. The operation disregards and does not
register car calls to pre-selected landings.
Generic Group Security
This feature utilizes keyswitches or clock inputs to cut off car and hall calls on
specified cars at specified landings through a software matrix setup.
Special Security
When Special Security operation is activated, all cars in the group return to the lobby
after first answering all pending car and hall calls. Once at the lobby, each car is
capable of answering a single hall call, after which it returns immediately to the lobby
and opens the car doors. When a hall call is entered, the following steps are
followed:
A car is dispatched from the lobby to answer the call. Each car is only
assigned a single hall call.
Once answered, no further hall calls are allowed for that car until it returns
to the lobby.
Once at the hall landing, if no car calls are entered, the car automatically
returns to its designated landing and opens its doors.
Car call security, if desired, is handled separately. To secure car calls, some variation of
Card Reader in Car security is suggested.
Hall Call Cut-Off—All Landings
Activating the keyswitch disables all hall calls. The car answers all registered car
calls parking itself at its last landing with the doors open.
Hall Call Cut-Off—Selected Landings
Hall Call Cut-Off operates from a keyswitch. The operation disregards and does not
register hall calls to pre-selected landings. All car calls are handled normally.