8 Searching for disruptions/troubleshooting
Sensor does not respond to the SDI-12 interface
Sensor correctly connected to a datalogger with SDI-12 input (master)?
Correct connection assignment.
Polarity of the supply voltage reversed?
Correct connection assignment.
Supply voltage < 9.6 V or > 28 V?
Adjust level of voltage supplied (check the length and cross-section of the
connection cable).
Is the supply voltage not direct current?
Only operate sensor with direct current.
Does the sensor address of the OTT PLS correspond with the sensor address
that the datalogger uses?
Correct sensor address.
4 20 mA loop current is missing
Is the sensor correctly connected to a datalogger or peripheral device with
4 ... 20 mA input (check polarity)?
Correct connection assignment.
Is the 4 .. 20 mA loop current correctly supplied through datalogger or OTT
PLS (internal/external supply)?
Correct connection assignment.
Measured value varies or is not present
Sensor dirty?
Clean sensor carefully. See Chapter 7, "Carrying out maintenance work".
Installation of the sensor steady (e.g. movement from swell)?
Optimize installation.
Drops of water in the pressure compensation capillary?
Replace pressure probe.
Status output at the 4 20 mA interface
The OTT PLS with 4 20 mA interface indicates the operational state or any
faults that might occur via the loop current:
Loop current Status
4 20 mA correct
3.4 mA FLASH memory defective
3.3 mA Watchdog error
3.2 mA Failed memory
3.1 mA Pressure cell defective
3.0 mA Analog converter defective
<3.0 mA Loop current error: broken line, loop supply missing
3.6 mA Measurement range not reached (underflow)
or global error
3.8 <4.0 mA Marginally below measurement range: The pressure
probe delivers an output signal proportional to the
water level, but is outside the specification (under range)
>20.0 20.5 mA Marginally above measurement range: The pressure
probe delivers an output signal proportional to the
water level, but is outside the specification (over range)
21.0 mA Measuring range exceeded (overflow)
Status output at the SDI-12 interface
see SDI-12 command aM1!