69
ADV/CC/ADVANCED--------P01
snooze now
< 0.6 amp
DOWN INC DEC PORT
ADV/CC/ADVANCED--------P01
wakeup mode
VOC change 1.5 V
DOWN INC DEC PORT
ADV/CC/ADVANCED--------P01
wakeup mode
time 5 minutes
DOWN INC DEC PORT
ADV/CC/ADVANCED--------P01
MPPT mode
auto track
DOWN INC DEC PORT
ADV/CC/ADVANCED--------P01
grid tie mode
non GT
DOWN INC DEC PORT
ADV/CC/ADVANCED--------P01
park MPP 77.0
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
Mpp range limit %VOC
minimum 1/2
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
Mpp range limit %VOC
maximum 90%
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
absorb time
1.0 hours
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
absorb end amps
0 A
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
rebulk voltage
12.4 vdc
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
vbatt calibration
13.3 vdc 0.0 V
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
RTS compensation
wide
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
RTS comp limit
upper limit 14.1 vdc
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
RTS comp limit
lower limit 13.2 vdc
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
auto restart
mode 2
DOWN INC DEC PORT
ADV/CC/ADVANCED------P01
reset CC to factory defaults
DOWN NO YES PORT
ADV/CC/ADVANCED---------
end CC advanced menu
TOP ADV MAIN
ADV------------------------------
choose device:
FX CC DC MATE
ADV/CC/PAGE 1 ----------------
choose category:
ADV CHGR CCADV PG2
ADV/CC/PAGE2----------------
choose category:
PG1 EQ AUX MAIN
24. Charge Controller Advanced Menu
ADV/CC/ADVANCED------P01
AUX output polarity
active high
DOWN INC DEC PORT

Table of Contents