EasyManua.ls Logo

oxycom IntrCooll Std. - Communication and Control Setup

oxycom IntrCooll Std.
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Prepare the location
Version 1.3, 2021-12-14 37
1
2
3
4
5
To fully isolate the IntrCooll® from the mains, Oxycom recommends the
installation of an external maintenance switch / padlock switch between the
unit's main connection and the mains AC supply. Make sure the installation is
executed according to local regulations.
Padlock switch (example)
a
b
1 Switch ON (unlocked)
2 Switch OFF (locked / unlocked)
An external automated circuit breaker is not included in the package and must be
provided and installed by the contractor.
3.15.4
Mains power outlet
Oxycom recommends to install a mains power outlet near the IntrCooll®. This can
be used by the service technician for maintenance equipment.
3.16
Communication requirements
There are several possibilities to control the IntrCooll®. The correct choice
depends on the situation and specic requirements.
3.16.1
Thermostat control
IntrCooll® can be controlled by a thermostat, unless it is controlled by a BMS
system. The thermostat must be ordered separately.
If more than one IntrCooll®s are available at the location, each IntrCooll® must be
connected to a separate thermostat, unless they are controlled with OxyConnect
gateway (optional) or a BMS system.
Note
See the documentation of the thermostat for information on the connection
cable to the IntrCooll® or OxyConnect.
Note
The cable is not included and must be provided by contractor.