Error codes on the OxyLogic LCD
Error code Error type
(1)
Description
Error 01 01(A) Tank ll takes too long; check water pressure or replace supply/drain valve (Port: 20/21).
Error 02 02(A) Measured ow while supply solenoid was closed; check or replace supply solenoid (Port: 20).
Error 03 03(B) Tank drain takes too long; clean drainpipe (clogged) or replace drain valve (Port: 21).
Error 04 04(B) Filter pressure exceeded; clean or replace lters.
Error 05 05(B) Level sensor shows deviating value; clean or replace level sensor(s) (Port: 5).
Error 06 06(B) Conductivity sensor shows deviating value; clean or replace sensor (Port: 15).
Error 07 07(A) Outdoor temperature sensor shows deviating value; check or replace sensor (Port: 1).
Error 08 08(B) Supply temperature sensor shows deviating value; check or replace sensor (Port: 3).
Error 09 09(B) No connection with thermostat or network (Modbus); check cables and parameters (Port: 16).
Error 10 10(A) Error supply fan; check cables and fan (Port: 13).
Error 11 11(A) Error exhaust fan; check cables and fan (Port: 14).
Error 12 12(B) Cooling performance below minimum value; check recirculation pump (Port: 18) and water distribution.
Error 13 13(A) System error.
(1)
Error type explanation:
- A = system locked
- B = maintenance required
5.3
Update rmware
5.3.1 Preparations
Requirements:
- Windows laptop
- UpdateTool *
- SettingsTool *
- Settings: Datale with PCB settings*
- Micro USB cable (A standard charger cable for mobile devices will not work.)
- Ethernet cable