Operation procedures
Version 1.3, 2021-12-14 55
1
2
3
4
5
5.1.4 How to switch the IntrCooll® o
There are several situations from which the IntrCooll® can be switched o. To
switch the IntrCooll® o:
- If the unit is on 'stand by', the main switch (1) can be switched o
immediately.
- If the IntrCooll® is in active cooling mode and a thermostat has been tted:
a) Set the on / o switch on the thermostat to o.
b) Switch o the main switch (1) on the IntrCooll®.
Warning
Do NOT turn o the IntrCooll® by interrupting the main voltage. The unit must
be able to fully run the automatic drying cycle.
Note
Legionella prevention. After switching o the system, the content of the water
tank is saved for a maximum of 60 minutes, after which it is automatically
emptied.
Note
If the IntrCooll did not receive a cooling request for an hour, the drying cycle
automatically starts. When the IntrCooll® cools the whole day, the drying cycle
starts at night (time set).
Note
The Oxyvap® pads need to dry to minimize bacterial growth. The silver ions in
the coating on the slats can kill the bacteria present.
Note
Only when the IntrCooll® is switched o for a shorter period of time (max
4 hours), can the drying cycle be skipped.
5.1.5 Switch o for longer periods
5.1.5.1 Take the IntrCooll® out of service
When the IntrCooll® is out of use for a longer period, obey the precautions below:
-
Make sure that no water remains in the sump, heat exchangers and Oxyvap®
media.
Normally the sump drains automatically when the IntrCooll® is de-energized.
- Disconnect the mains water connection and bleed the water supply line.