4. Save setting: Press navigation button [1] and [2] simultaneously for two
seconds.
5. Conrm and exit: Press navigation button [1].
Settings menu
Settings value Value IntrCooll Std
Factor default
IntrCooll Plus
Factor default
Unit Brief discription
S01: Filtertype Setting - - Select used lter medium.
S02: LevelsensL Setting 10 10 Do not change this parameter.
S03: LevelsensH Setting 10 10 Do not change this parameter.
S04: Drain delay Setting 60 60 Minutes Delay for draining the tank completely
after cooling.
S05: Drian duration Setting 90 90 Seconds Short drain duration (during operation
when conductivity exceeds limit), can be
set
S06: Max Conductivity Setting 1250 1250 μS/cm Conductivity limit for recirculation water
(maximum is 1250μS/cm and/or 10
cycles of concentration - above this value
calcium will deposit at increased rates).
S07: OverowProt Setting 15 15 Seconds Overow protection timer (opening itme
of drain valve when level high is
reached).
S08: Rinse Setting 10 10 Seconds Flsuh duration after draining (opening
time of supply solenoid).
S09: Heat Reclaim Setting O O Enable of disable HeatReclaim (heating)
mode (enable when Heat Reclaim or 4S
module is used for this unit).
S10: Operation Method Setting Automatic Automatic Manually select operation mode for
maintenance (saving settings required to
activate / do not forget to switch back to
automatic and save again).
S11: Fan Speed Setting Automatic Automatic Manually select fan speed for
maintenance (saving settings required to
activate / do not forget to switch back to
automatic and save again).
S12: Min Fan Heating Setting 75 59 % Minimum fan speed for Heat Reclaim
(only change when approved by Oxycom
or representative).
S13: Max Fan Heating Setting 75 59 % Maximum fan speed for Heat Reclaim
S14: Min Fan Free
Cooling
Setting 30 30 % Minimum fan speed for free-cooling
62