6. When the "bootloader" is ready (see OxyLogic LCD), press the reset button [3]
on the OxyLogic.
OxyLogic will now restart and the system is ready.
7. Disconnect the USB.
Set the language:
1. Enter the Settings menu by pressing buttons [1] and [2] simultaneously on
OxyLogic for 2 seconds.
2. Press button [2] to scroll to setting "S30".
3. Use button [1] to scroll to "Preferred language".
4. Press buttons [1] and [2] simultaneously for 2 seconds.
5. Press button [2] to save and conrm.
6. To implement the new rmware, switch o the IntrCooll® for one minute
using the main switch.
5.3.3
Update procedure (Ethernet)
Update rmware on the IntrCooll® using Ethernet:
1. Connect Ethernet cable to the OxyLogic module.
2. Connect the Ethernet cable to the laptop.
3. Congure the LAN settings on the laptop:
• IP-adres: 192.168.0.30
• Subnet: 255.255.255.0
• Gateway: 192.168.0.1
4. Right mouse click on "UpdateTool" le and click "Run as administrator"
(important).
5. The UpdateTool opens.
6. Click on "Select port: Ethernet". And type in the same IP-adres as above.
7. Click on "Load rmware" and select the rmware le in the folder "Software".
8. The UpdateTool shows "Software updated" when the update is complete.
9. When the "bootloader" is ready (see OxyLogic LCD), press the reset button [3]
on the OxyLogic.
10. OxyLogic will now restart and the system is ready.
11. Disconnect the Ethernet cable.