< When hot start operation is cancelled by temperature >
26.5. Indoor unit fan control when thermostat is off during heating mode
operation
When the thermostat of the indoor unit turns off during heating mode operation, the indoor unit fan operates for 2 minutes at LOW
and then stops. In addition, 5 minutes after the thermostat of the indoor unit turns off, the indoor unit fan again runs at LOW for 10
seconds, and at 3-minute intervals after that it switches back to LOW operation for 10 seconds.
26.6. Excess heat dissipation for indoor unit
The indoor unit fan continues operating for 30 seconds after heating mode operation turns off in order to
dissipate excess heat.
1. When heating mode operation has stopped
(LOW operation for 30 seconds)
2. When operation is set to a mode other than heating by means of the OPERATION MODE switch
3. If operation starts again during the 30 seconds mentioned in (1) above