27.5. Hot starting
1. When heating mode operation starts
a. Start
Hot start control commences when heating mode operation starts.
b. Operation
“PREHEAT” appears on the remote control display. (Other displays remain unchanged.)
The indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal position (angle 0°).
c. Cancelling
Hot starting will be cancelled when the compressor is turned on or the indoor unit pipe temperature sensor is 18°C or higher
or after 1 minute of operation.
After cancellation, the “PREHEAT” display on the remote control disappears and the louvre operation returns to the previous
setting.
(However, for 2 minutes after cancellation, the indoor unit fan operates at LOW speed, and then returns to the previous
setting.)
<When hot start operation is cancelled by temperature>
<When hot start operation is cancelled by time>