Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Compressor Protection Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
•
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
•
During Soft Dry operation, the Indoor Fan will operate at low speed.
•
The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
•
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
•
Same as Starting Current Control for Cooling Mode operation.
•
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
•
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
•
Same as Compressor Protection Control for Cooling Mode Operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
•
Fan speed off and on at Lo speed.
•
Deodorizing Control.
20
S-A75KE CU-A75KE / CS-A95KE CU-A95KE / CS-A125KE CU-A125KE