37 
[Heating] 
  According to indoor pipe temperature, automatic heating fan speed is determined as follows. 
 
 
 
B. Feedback control 
  Immediately after the fan motor started, feedback control is performed once every second. 
  During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error 
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan 
motor error is detected. Operation stops and cannot on back. 
12.3  Outdoor Fan Motor Operation 
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 
seconds after compressor stops operation. 
 
 
12.4 Airflow Direction 
  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by 
vertical vanes). 
  Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat 
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using 
remote control). 
12.4.1 Vertical Airflow 
 
Operation Mode 
Vane Angle (°) 
1 2 3 4 5 
Cooling 
Auto 
Usual (Ventilation)  10 ~ 40 
Control with dew  10 ~ 40 
Manual 
Usual (Ventilation) 10 17.5 25 32.5 40 
Control with dew  10 17.5 25 32.5 40 
Dry 
Auto 
Usual  10 ~ 40 
Control with dew  10 ~ 40 
Manual 
Usual  10 17.5 25 32.5 40 
Control with dew  10 17.5 25 32.5 40 
Heating 
Manual  Usual  10  21.2 32.5 43.8  55 
Auto 
A 10 
B 43.8 
C 21.2