14.2.2 Operation mode during Heating Only Operation 
  The table below shows the operation mode comparison when Heating Only Operation Mode Activated and 
Deactivated. 
 
Operation Mode  Heating Only Operation Mode Activated  Heating Only Operation Mode Deactivated 
AUTO 
After 30s sampling, regardless of the indoor intake or 
outdoor intake temperature judgment, the unit will run 
Heating operation. 
After 30s sampling, the unit will judge the operation 
mode base on remote controller temperature setting 
and Indoor Intake Sensor (New Auto Mode) or 
Outdoor Intake Sensor (Old Auto Mode). 
HEAT  The unit will run Heating operation.  The unit will run Heating operation. 
COOL  The unit will stop and Power LED blinking.  The unit will run Cooling operation. 
DRY  The unit will stop and Power LED blinking.  The unit will run Cooling Dry operation. 
NANOE-G Stand-alone  The unit will stop and Power LED blinking.  The unit will run Nanoe-G Stand-alone operation. 
Force Cooling 
The unit will run Force Cooling Operation for 
X_CTRYTM [15] minutes 
The unit will run Force Cooling operation. 
Force Heating  The unit will run Force Heating operation.  The unit will run Force Heating operation. 
AUTO (with Timer) 
The unit will turn ON by the timer and run Auto 
Operation. After 30s sampling, regardless of the 
indoor intake or outdoor intake temperature judgment, 
the unit will run Heating operation. 
The unit will turn ON by the timer and run Auto 
Operation. After 30s sampling, the unit will judge the 
operation mode base on remote controller 
temperature setting and Indoor Intake Sensor (New 
Auto Mode) or Outdoor Intake Sensor (Old Auto 
Mode). 
HEAT (with Timer) 
The unit will turn ON by the timer and run Heating 
Operation. 
The unit will turn ON by the timer and run Heating 
Operation. 
COOL (with Timer) 
The unit will not turn ON by the timer. Power LED 
blinking. 
The unit will turn ON by the timer and run Cooling 
Operation. 
DRY (with Timer) 
The unit will not turn ON by the timer. Power LED 
blinking. 
The unit will turn ON by the timer and run Cooling Dry 
Operation. 
Cooling Test Mode  The unit will stop and Power LED blinking. 
The unit will operate according to specify Cooling test 
mode operation parameter. 
Heating Test Mode 
The unit will operate according to specify Heating test 
mode operation parameter. 
The unit will operate according to specify Heating test 
mode operation parameter. 
14.3 Remote Control Button 
14.3.1 SET Button 
  To check remote control transmission code and store the transmission code to EEPROM: 
o  Press “Set” button by using pointer. 
o  Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code changed. 
  To limit set temperature range for COOL & DRY, HEAT mode. 
o  Press “Set” button by using pointer. 
o  Press TEMP increment or decrement button to choose No. 3. 
o  Press Timer increment or decrement button to select desired temperature low limit of set temperature for 
COOL & DRY mode. 
o  Press Timer Set button to confirm low limit selection. 
o  Press TEMP increment or decrement button to choose No. 4. 
o  Press Timer decrement or increment button to select desired temperature high limit of set temperature for 
COOL & DRY mode. 
o  Press Timer Set button to confirm high limit selection. 
o  Press TEMP increment or decrement button to choose No. 5. 
o  Press Timer increment or decrement button to select desired temperature low limit of set temperature for 
HEAT mode. 
o  Press Timer Set button to confirm low limit selection. 
o  Press TEMP increment or decrement button to choose No. 6. 
o  Press Timer decrement or increment button to select desired temperature high limit of set temperature for 
HEAT mode. 
o  Press Timer Set button to confirm high limit selection. 
o  LCD returns to original display if remote control does not operate for 30 seconds or press Timer Cancel 
button. 
14.3.2 RESET (RC) 
  To clear and restore the remote control setting to factory default. 
o  Press once to clear the memory.