94
18. Service Data
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
18.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
- Indoor room temperature: 27°C Dry Bulb/19°C Wet Bulb
- Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
- Compressor frequency: Rated for cooling operation
- Piping length: 5m
- Voltage: 220-230V (CS/CU-BE25TKE-1), 230V (CS/CU-DE25TKE-1)
18.1.1 CS-BE25TKE-1 CU-BE25TKE-1
Outdoor Air Temperature (°C)
Outdoor Air Temperature (°C)
Current (A)
Outdoor Air Temperature (°C)
Indoor Discahrge
Air Temperature (°C)Low Pressure (MPa)
220V 230V
12 16 20 24 28 32 36 40 44 48
12 16 20 24 28 32 36 40 44 48
12 16 20 24 28 32 36 40 44 48
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
12.00
13.00
14.00
15.00
16.00
17.00
18.00
19.00