15.5.5  H16 (Outdoor Current Transformer) 
Malfunction Decision Conditions 
  An input current, detected by Current Transformer CT, is below threshold value when the compressor is 
operating at certain frequency value for 3 minutes. 
 
Malfunction Caused 
  Lack of gas 
  Broken CT (current transformer) 
  Broken Outdoor PCB 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
For safety reason and to prevent
component breakdown, always switch 
off the power before remove and 
connect the component.
Refer to Service Manual Technical Graph 
for Temp vs Current and Pressure
In forced cooling, check suction ressure 
versus running current
Running current and suction pressure is 
very low
When abnormality indication starts again.
Check for gas leaking source; Repair 
or replace defected part(s)
Capillary tube/expansion valve 
blockage; Replace defected part(s)
Running current is much too low and 
suction pressure is much too high
Caution
Compressor Lack Compression
Replace Compressor
Suction pressure and running current is 
normal
Check & replace defected CT