How to use electronic circuit diagram
TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Sleep Mode Waiting 1 hr. 6 sec.
Sleep Mode Operation 8 hrs. 48 sec.
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 42 sec.
Anti-Freezing 4 min. 0 sec.
Mode Judgement 20 sec. 0 sec.
Soft OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Deodorizing Control
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
20 sec. 2 sec.
Soft Dry 180 sec. 18 sec.
40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Intake Air Anti-Freezing Prevention 16 min. 96 sec.
Powerful Mode 15 min. 15 sec
Random FM Timer (Economy Mode) 5 sec. 5 sec.
Random Auto Restart Control 0 ~ 150 sec. 0 sec.
85
CS-C75KE CU-C75KE / CS-C95KE CU-C95KE / CS-C125KE CU-C125KE