12
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb)
and outdoor air temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry
Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
Note
• Specifications are subject to change without notice for further improvement.
Fan
Type Backward Fan Propeller Fan
Material ABS + GF 10% PP
Motor Type DC Brushless Motor (8-pole) Transistor (8-pole)
Output Power W 40 40
Fan Speed
QLo (Cool/Heat) rpm 480 / 560 —
Lo (Cool/Heat) rpm 510 / 580 —
Me (Cool/Heat) rpm 605 / 675 —
Hi (Cool/Heat) rpm 700 / 770 700 / 680
SHi (Cool/Heat) rpm 750 / 820 —
Heat Exchanger
Fin Material Aluminium (Pre Coat) Aluminium
Fin Type Slit Fin Corrugated Fin
Row x Stage x FPI 2 × 10 × 18 2 × 34 × 18
Size (W x H x L) mm
1330 × 210 × 25.4 36.4 × 714 × 823.2
1270 851.9
Item Unit
Power Source (Phase, Voltage, Cycle)
øSingle
V 230 - 240
Hz 50
Input Power W
Cooling; 2.05k (255 ~ 2.20k)
Heating; 2.45k (260 ~ 2.82k)
Starting Current A 10.9
Running Current A
Cooling; 9.2 - 9.0
Heating; 10.9 - 10.6
Maximum Current A 12.6
Power Factor %
Cooling; 97 - 95
Heating; 98 - 96
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
Number of core
—
Length m
—
Thermostat Electronic Control
Protection Device Electronic Control
ITEM UNIT INDOOR UNIT OUTDOOR UNIT