12.8. Drain Pump Control Operation
To drain out the condensed watar trapped in the drain pan in order to prevent the condensed water from overflowing from the
drain pan and leaking.
Drain Pump starts to operate 10 sec. after compressor and Indoor fan ON.
Drain Pump stop to operate 90 sec. after compressor OFF.
Drain Pump Error
Drain Pump Error occurs when:
- Within 20 minutes, the float switch is ON twice.
- Float switch is ON continuously for 2 minutes 30 seconds.
When error occurs, the timer indicator blinks and the unit stops its operation.