14.4.3  H14 (Indoor Intake Air Temperature Sensor Abnormality) 
Malfunction Decision Conditions 
•  During startup and operation of cooling and heating, the temperatures detected by the indoor intake air 
temperature sensor are used to determine sensor errors. 
 
Malfunction Caused 
• Faulty connector connection. 
• Faulty sensor. 
• Faulty PCB. 
 
Troubleshooting 
 
Sensor (Thermistor)
Characteristics
70
60
50
Resistance (kΩ)
Temperature (ºC)
40
30
20
10
-10 0 10 20 30 40 50
0
1 Pipe temp. Sensor
2  Intake Air Temp. Sensor
1
2
 
When abnormality indication starts again 
Check the indoor intake air temperature sensor: 
•  Plug out connector from the indoor unit PCB 
•  Measure the resistance of the indoor intake air 
temperature sensor 
For safety reason and to prevent component 
breakdown, always switch off the power 
before remove and connect the component. 
Is the measured resistance of the indoor intake air 
temperature sensor matches the value specified in its 
characteristic chart? 
  Defect in indoor unit PCB 
•  Replace the indoor unit PCB 
Check the connector connection: 
•  Turn off the power 
•  Check the connector connection 
Is the connector connection normal? 
YES