14.4.4  H15 (Compressor Temperature Sensor Abnormality) 
Malfunction Decision Conditions 
•  During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor 
temperature sensor are used to determine sensor errors. 
 
Malfunction Caused 
• Faulty connector connection. 
• Faulty sensor. 
• Faulty PCB. 
 
Troubleshooting 
 
Compressor Temp. Sensor
(Thermistor) Characteristics
70
60
50
Resistance (kΩ)
40
30
20
10
0
Temperature (ºC)
20 40 60 80 100 120 140
 
When abnormality indication starts again 
Check the outdoor compressor temperature sensor: 
•  Plug out connector from the outdoor unit PCB 
•  Measure the resistance of the outdoor compressor 
temperature sensor 
For safety reason and to prevent component 
breakdown, always switch off the power 
before remove and connect the component. 
Is the measured resistance of the outdoor compressor 
temperature sensor matches the value specified in its 
characteristic chart? 
  Defect in outdoor unit PCB 
•  Replace the outdoor unit PCB 
Check the connector connection: 
•  Turn off the power 
•  Check the connector connection 
Is the connector connection normal? 
YES