49 
14.4.5  H16 (Outdoor Current Transformer Open Circuit) 
Malfunction Decision Conditions 
•  A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and 
CT detected input current (less than 1.14A) for continuously 20 seconds. 
 
Malfunction Caused 
• CT defective 
•  Outdoor PCB defective 
•  Compressor defective (low compression) 
 
Troubleshooting 
 
When abnormality indication starts again 
 
Check the functionality of current transformer (CT) 
  Replace the outdoor PCB 
For safety reason and to prevent 
component breakdown, always switch 
off the power before remove and 
connect the component. 
Is the running current less than 0.65A and suction pressure 
120psi? 
YES  
NO 
YES  
NO