EasyManua.ls Logo

Panasonic CS-S18PKH

Panasonic CS-S18PKH
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124
15.4.22 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
Outdoor pipe temperature rise due to defective of outdoor fan motor.
Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting

Table of Contents

Related product manuals