15.4.23 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling, when IPM temperature data (100°C) is detected by the IPM temperature sensor.
Malfunction Caused
IPM overheats due to short circuit of hot discharge air flow.
IPM overheats due to defective of outdoor fan motor.
IPM overheats due to defective of internal circuitry of IPM.
IPM overheats due to defective IPM temperature sensor.
Troubleshooting