15.4.26 F99 (DC Peak Detection)
Malfunction Decision Conditions
During startup and operation of cooling, when inverter DC peak data is received by the outdoor internal DC peak
sensing circuitry.
Malfunction Caused
• DC current peak due to compressor failure.
• DC current peak due to defective power transistor (IPM).
• DC current peak due to defective outdoor unit PCB.
• DC current peak due to short circuit.
Troubleshooting