15.4.25 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling operation, when an input over-current is detected by checking the input current value being detected
by current transformer (CT) with the compressor running.
Malfunction Caused
• Over-current due to compressor failure.
• Over-current due to defective outdoor unit PCB.
• Over-current due to defective inverter main circuit electrolytic capacitor.
• Over-current due to excessive refrigerant.
Troubleshooting
Model S10** S13** S15** S18** S24**
Over-current
value (A)
15.0 15.0 15.0 15.0 19.0