94
13.5 Compressor Overheating Prevention Control (For S18, S24PK only)
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. “F97” is indicated.
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
103°C
87°C
99°C
96°C
88°C
86°C
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
112°C
96°C
110°C
100°C
97°C
90°C
(S18PK only)
13.6 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happened 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
13.7 Compressor Tank Temperature Rise Protection Control
Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
Control contents
o Compressor stops (and restart after 3 minutes)
o If the conditions above happened 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
13.8 Low Frequency Protection Control 1
When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
13.9 Low Frequency Protection Control 2
When all below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for: Cooling / Soft Dry
Indoor intake air (°C) T < 15 or T 30
Outdoor air (°C) T < 16 or T 38
Indoor heat exchanger (°C) T < 30