13.5 Compressor Overheating Prevention Control (For S18, S24PK only)
• Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
• If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. “F97” is indicated.
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
103°C
87°C
99°C
96°C
88°C
86°C
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
112°C
96°C
110°C
100°C
97°C
90°C
(S18PK only)
13.6 Low Pressure Prevention Control (Gas Leakage Detection)
• Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
• Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happened 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
13.7 Compressor Tank Temperature Rise Protection Control
• Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
• Control contents
o Compressor stops (and restart after 3 minutes)
o If the conditions above happened 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
13.8 Low Frequency Protection Control 1
• When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
13.9 Low Frequency Protection Control 2
• When all below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for: Cooling / Soft Dry
Indoor intake air (°C) T < 15 or T ≥ 30
Outdoor air (°C) T < 16 or T ≥ 38
Indoor heat exchanger (°C) T < 30