EasyManua.ls Logo

Panasonic CS-TZ25TKEW

Panasonic CS-TZ25TKEW
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
123
18.4.26 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the
compressor tank temperature sensor.
Malfunction Caused
Faulty compressor tank temperature sensor
2/3 way valve closed
Refrigerant shortage (refrigerant leakage)
Faulty outdoor unit PCB
Faulty compressor
Troubleshooting
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Table of Contents

Other manuals for Panasonic CS-TZ25TKEW

Related product manuals