122 
16.3.5  Cold Draught Prevention Control 
  When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced. 
16.3.6 Deice Operation 
  When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor 
and outdoor fan motor stop and operation LED blinks. 
16.3.7  Low Pressure Protection Control 
  During low ambient heating operation, if the pipe temperature drops below -22°C, the max frequency will be 
reduced and limited. 
  If it does not rises after 3 minutes, the compressor will stop. 
  The compressor will start again if the pipe temperature rises above -18°C.