90 
13.5  Piping installation of R32 
13.5.1  Pipe materials used and flaring 
Copper pipes are used for refrigerant piping. Pipes 
which comply with JIS Regulations need to be used. 
Room air conditioners which use R410A and R32 
have higher pressure; thus, using pipes which comply 
with the Regulations is important. 
The pipe thickness is regulated by revised JIS B 8607 
“Flaring and brazing fittings for refrigerant” and the 
pipe thickness for R410A, R32 is shown in the table. 
 
 
 
Pipe thickness 
 
O and OL materials  Thickness (mm) 
Diameter 
Diameter 
(mm) 
R410A  R32  R22 
1/4  6.35  0.80 
3/8  9.52  0.80 
1/2  12.70  0.80 
5/8  15.88  1.00 
 
Caution 
  For connection piping, use copper phosphate seamless pipes (1220T) as regulated in “JIS H 3300” and the pipe 
thickness is 0.8 mm. 
  In the market, there are some pipes of 0.7 mm thickness, but do not use these pipes (0.8 mm thickness has to be 
strictly followed). 
  It is recommended to use pipes whose adhesion amount of oil is at or less than 40 mg / 10 m. 
At the same time, do not use pipes with dent, de-shape, and color change (especially inside). 
13.5.2 Processing and connection of pipes 
For refrigerant pipe installation, be aware of moisture and dirt do not get into the pipes, and make sure of no 
refrigerant leakage. 
◎ The procedure of flaring and precautions 
a)  Cutting of pipes:use pipe cutter and cut the pipe slowly not to de-shape the pipe. 
b)  Removal of burrs on the edge of pipe (reamer or scraper) 
If the condition of pipe edge after the deburring is no good or if burrs attaches on the flaring, it may cause 
refrigerant leakage. Turn the pipe end down and perform deburring carefully. 
c)  Insert the flare nut (use the nut which is a part of the CZ parts) 
d)  Flaring 
Ensure the cleanliness of clump bar and pipe, and perform flaring carefully. 
Use the existing flare tools or flare tools for R410A. Be aware that the sizes and dimensions of flaring is different 
in each flaring tool. If you use the existing flaring tools, use flaring gauge to measure the length of the flaring part. 
 
Piping 
size 
(mm) 
Dimensions “a” (mm) 
R22 
Dimensions “a” (mm)  
R410A/R32 
 
Nut outer diameter (mm)
Flare tools 
Flare tools 
for R410A 
Flare tools 
Flare tools 
for R410A 
R22 
R410A 
Clutch type 
Wing nut 
type 
Clutch type  Clutch type
Wing nut 
type 
Clutch type R32 
6.35 (1/4")  0.5 ~ 1.0  1.0 ~ 1.5  0 ~ 0.5  1.0 ~ 1.5  1.5 ~ 2.0  0 ~ 0.5  17  17 
9.52 (3/8")  0.5 ~ 1.0  1.0 ~ 1.5  0 ~ 0.5  1.0 ~ 1.5  1.5 ~ 2.0  0 ~ 0.5  22  22 
12.70 (1/2")  0.5 ~ 1.0  1.5 ~ 2.0  0 ~ 0.5  1.0 ~ 1.5  2.0 ~ 2.5  0 ~ 0.5  24  26 
15.88 (5/8")  0.5 ~ 1.0  1.5 ~ 2.0  0 ~ 0.5  1.0 ~ 1.5  2.0 ~ 2.5  0 ~ 0.5  27  29 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
a
Bar