18.4.2  H12 (Indoor/Outdoor Capacity Rank Mismatched) 
Malfunction Decision Conditions 
  During startup, error code appears when different types of indoor and outdoor units are interconnected. 
 
Malfunction Caused 
  Wrong models interconnected. 
  Wrong indoor unit or outdoor unit PCBs mounted. 
  Indoor unit or outdoor unit PCBs defective. 
  Indoor-outdoor unit signal transmission error due to wrong wiring. 
  Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor 
and outdoor units. 
 
Troubleshooting