(Cooling and Soft Dry Operation condition)
8.9. Powerful Operation
  • The Powerful operation is to achieve the setting temperature quickly.
  • When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
  • This operation automatically will be running under SHi Fan Speed (Cooling).
  • Vertical Airflow Direction:-
-In“Manual” setting, the vane will automatically shift down 10° lower than previous setting.
-In“Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
  • Powerful operation stops when:-
  − Powerful operation has operate for 15 minutes.
  − Powerful button is pressed again.
  − Quiet button is pressed.
  − Stopped by OFF/ON operation button.
  − Timer OFF activates.
  − Operating mode is changed.
8.10. Quiet Operation
  • The Quiet operation is to provide quiet cooling/heating operation condition compare to normal operation.
(Cooling and Soft Dry Operation condition)
  • Once the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around
2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation.
  • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo
+ 100 rpm). After that, it goes back to QLo +180 rpm (However Quiet LED remains on).
  • Manual Fan Speed:-
  − RPM control during Lo cool
  − RPM control during Hi & Me cool