5-4. Inspection of Parts (Outdoor Unit)
Mini VRF SYSTEM
Trouble Diagnosis
5. Inspection of Parts (Outdoor Unit)
(1) Electronic control valve (MOV1)
(2) Outdoor Unit Fan Motor
Model No. Part No. (Panasonic) Part No.
L6CBYYYL0296 NFD-81FW-D8120-6
L6CBYYYL0297 NFD-81FW-D8120-7
U-200PZH2E8, U-250PZH2E8
MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN-MOV1 connector (5P, white)
on the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used.
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
If the voltage is normal, measure the resistance between connector pin 5 and pins 1 through 4.
Resistance between pin 5 and pins 1 through 4 should be approximately 46 ohm for all. (If the result is 0 ohm
or, then replace the coil.)
SM830195-00.indb52 2011/09/3015:41:52
(3) Coil Resistance of Compressor
Part No.Model No.
9VD550XAA21U-200PZH2E8
Part No.
(Panasonic)
ACXB09-07100
9VD550XAA21U-250PZH2E8
ACXB09-07100
U - VV - W
0.735 0.715
U - W
0.715
0.735 0.715 0.715
Inverter compressor (at 20°C)
SM830276-00_欧州向け R32シングル TD&SM.indb 32 19/02/28 13:29:41