1-7-1
1
60
80
80
60
40
100
120
140
352515 455-15
100
120
-5 -10 50 10-5
120
40
60
80
100
120
40
60
80
100
15 20-25 -15-20
Input coefficient (%) Capacity coefficient (%)
Input coefficient (%) Capacity coefficient (%)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
1-7. Capacity Correction Graph According to Temperature Condition
U-200PZH2E8 / U-250PZH2E8 (For 50 Hz)
Indoor air intake temp (WB)
19WB
16WB
22WB
22WB
19WB
16WB
Indoor air intake temp (WB)
Outdoor air intake temp (°C DB)
16
°C
20
°C
24
°C
Outdoor air intake temp (°C WB)
24
°C
20
°C
16
°C
1. The graphs " " of the characteristics show the value under the following conditions.
Equivalent tubing length : 7.5m
Difference of elevation : 0m
Wind speed : High
2. " " marking indicates the maximum capacity / maximum power consumption.
Maximum capacity indicates the maximum value in the parentheses of the specifications (cooling and heating capacity).
3. The characteristic of heating capacity excludes the decline of capacity when frosting (including defrost drive).
NOTE 1
Indoor air intake temp (
°C
DB)
Indoor air intake temp (
°C
DB)
Outdoor unit heating capacity correction cofficient during of frosting/defrosting
Outdoor intake air
temperature °C WB
-20
0.880
-21
0.880 0.880 0.880 0.880 0.880 0.880 0.860 0.830 0.8300.8800.8800.8800.8800.8800.8800.8800.8800.880
0.820 0.820 1.0000.9500.9100.8900.8500.8300.830
-19 -18 -17 -16 -15 -14 -13 -12 -11
-10
-9 -8
Correction coefficient
Outdoor intake air
temperature °C WB
Correction coefficient
-1 0 1 2 3 4 5 6-2
-7 -6 -5 -4 -3
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.