77
Item code Item
Setting data
No. Description
Automatic drain pump
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060
Continuous operation
Ventilation fan operation
0000
None
0001 Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000 Not used. (Body sensor is used.)
0001
Remote controller sensor is used.
“Operation change control in
progress” display
0000
Normal (displayed)
0001
Not displayed
OFF reminder function for
when weekly timer is used
0000 None
0001
Only stop time setting is enabled.
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
0013 Control temperature 13°C
0014 Control temperature 14°C
0025 Control temperature 25°C
0026 Control temperature 26°C
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed stop
time
0000 No delayed stop
0001 1 min. delayed stop
0002 2 min. delayed stop
0058 58 min. delayed stop
0059 59 min. delayed stop
0060 60 min. delayed stop
Flap operation mode
0000 Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted
upwards.)
Flap swing mode
0000
Smudging reduction mode (Flap swing upper-limit position is
shifted downwards.)
0001 Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is shifted
upwards.)
(Continued)
7-9
SM830276-00_欧州向け R32シングル TD&SM.indb 9 19/02/28 13:33:39