Control of 2WAY SYSTEM
2. Wireless Remote Controller
4. Setting Address Switches
5. Test operation
Main/Sub setting Address setting
Remove the top case of the receiver for setting.
Main/Sub setting
1 2 3 4
Switch
ONOFF
Use this to set Main/Sub for the remote controller and the receiver.
Set one to [Main] and the other to [Sub].
Factory default: [Main]
It is recommended to set the wired remote controller to [Main].
BUSNIAMbuS/niaM
Main/Sub switch position
123 4
123 4
Address setting
When more than 1 receiver is installed in the same room, setting addresses prevents interference.
For how to change addresses of wireless remote controllers, see operating instructions of wireless remote controllers.
Wireless
remote controller
address display
Address Address Address Address Address Address Address
ALL 12345 6
Address
switch position
Receiving is
possible at all
address positions.
123 4 123 4 123 4 123 4 123 4 123 4
Preparation :
Turn on the circuit breaker of units and then turn the power on. After the power is turned on, remote controller operation is ignored
for approx. 1 minute because setting is being made. This is not malfunction. (Contents received while setting are disabled.)
1. To start test operation, press and hold the emergency operation button for 10 seconds.
2. The indication lamps (OPERATION, TIMER, STANDBY) blink during test operation.
.sdnoces 01 rof nottub noitarepo ycnegreme eht dloh dna sserp ,noitarepo tset hsin if oT .3
Attention
Do not use this mode for purposes other than the test operation.
(To prevent overload of the units)
Read the installation instructions supplied with the units.
Any of the Heat, Cool and Fan operations can only be performed.
Temperature cannot be changed.
The test operation mode is automatically turned off in 60 minutes.
(To prevent continuous test operation)
Outdoor units do not operate for approx. 3 minutes after the power is
turned on or operation is stopped.
Self-diagnostics table and detected contents
The "Alarm Display" as shown in the table below expresses the alarm contents displayed when the wired remote controller is connected. For
how to handle the alarms, see installation instructions of indoor units or technical guide.
reviecerehtnopmalnoitacidnIstnetnocdetceteD
Alarm Display
OPERATION TIMER STANDBY
Blinking
E01–E03, E08–E14, E17, E18
Communication error either in the in/outdoor operation line or
the sub-bus of the outdoor unit
E04–E07, E15, E16, E19–E31
Operation of indoor protection device
P01, P09–P14
Alternately
13P51P,80P20PecivednoitcetorproodtuofonoitarepO
Alternately
11F01F,30F10FrotsimrehtroodniehtnirorrE
Alternately
82F21F,90F40FrotsimrehtroodtuoehtnirorrE
Alternately
92FMORPEEroodniehtnirorrE
Simultaneously
13F,03FMORPEEroodtuoehtnirorrE
Simultaneously
13H10HrosserpmocehtotdetalerrorrE
90L50L,30L10LsgnittesroodninirorrE
Simultaneously
13L01L,40LsgnittesroodtuonirorrE
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting
for a model without auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test operation
Simultaneously
: OFF : ON (Illuminated) : Blinking (0.5 seconds interval)
Communication error in the remote controller circuit
Sec8.indd30 2012/02/2816:14:03
SM830256-00_Single_欧州小筺体 TD&SM.indb 24 16/12/28 13:40:36
The “Alarm Display” shown in the table below expresses the alarm contents displayed when the
wired remote controller is connected. For how to handle the alarms, see installation instructions of
indoor units, “Service Manual”, “Test Run Service Manual”.
Indication lamp on the receiver
Detected contents
Alarm Display Blinking
OPERATION TIMER STANDBY
Communication error in the remote
controller circuit
E01–E03, E08–E14,
E17, E18
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16,
E19–E31
Operation of indoor protection device
P01, P09–P14
Alternately
Operation of outdoor protection device P02–P08, P15–P31
Alternately
Error in the indoor thermistor F01–F03, F10–F11
Alternately
Error in the outdoor thermistor F04–F09, F12–F28
Alternately
Error in the indoor EEPROM F29
Simultaneously
Error in the outdoor EEPROM F30, F31
Simultaneously
Error related to the compressor H01–H31
Error in indoor settings L01–L03, L05–L09 Simultaneously
Error in outdoor settings L04, L10–L31
Simultaneously
Error in the gas heat pump air
conditioner
A01–A31
Simultaneously
Inconsistency in Cooling/Heating (Including an auto-temp
setting for a model without auto-temp settings)
Alternately
Oil alarm (Same as operation of outdoor protection device)
Auto addressing in progress (when it is performed with an infrared
remote controller)
Alternately
Test operation
Simultaneously
: OFF : ON (Illuminated) : Blinking (0.5 seconds interval)
2. Room Temperature Sensor Settings
Only arailable to CZ-RWSK2, CZ-RWSU3
8-35. Common to All Models
1. The Self-Diagnosis Function Display and What is Detected
The indoor unit and the wireless remote controller are equipped with room temperature
sensors. The sensing of room temperature works via one of them.
When the unit is shipped, it is set to the indoor unit. To switch it to the remote controller,
press the sensor button (the fi gure on the right) inside the remote controller’s cover
and then check that Main Sensor  on the LCD screen goes off.
Be sure to install the remote controller so as to face the receiver.
If the unit does not receive any room temperature data from the remote controller
for ten minutes even with its sensing function activated, the indoor unit sensor will
automatically start sensing the room temperature.