Error
code
Name
Opera-
tion
status
Description and steps to take
FP-e
FP0
FP0R
FP
FP-X
FP-X0
FP2
FP2SH
FP10SH
E6
Compile
error
Stops
The program is too large to compile in the
program memory.
⇒ Change to PROG. mode and reduce the
total number of steps for the program.
-FP10SH
If memory expansion is possible, compilation
will become possible when the memory is
A A A A A A A A
E7
High-level
instruction
type error
Stops
In the program, high-level instructions, which
execute in every scan and at the leading
edge of the trigger, are programmed to be
triggered by one contact. (e.g. F0 (MV) and
P0 (PMV) are programmed using the same
trigger continuously.)
⇒ Correct the program so that the high-level
instructions executed in every scan and only
at the leading edge are triggered separately.
A A A A A A A
E8
High-level
instruction
operand
combina-
Stops
There is an incorrect operand in an
instruction which requires a specific
combination of operands (for example, the
operands must all be of a certain type).
⇒ Enter the correct combination of operands.
A A A A A A A A A
E9
Stops
Program may be damaged.
⇒Try to send the program again.
A A
E10
Rewrite
during
RUN
syntax
error
Conti-
nues
When inputting with the programming tool
software, a deletion, addition or change of
order of an instruction(ED, LBL, SUB, RET,
INT, IRET, SSTP, and STPE) that cannot
perform a rewrite during RUN is being
attempted. Nothing is written to the CPU.
A A A