code
Name
Opera-
tion
status
Description and steps to take
FP-e
FP0
FP0R
FP
Σ
FP-X
FP-X0
FP2
FP2SH
FP10SH
E29
Configu-
ration
parameter
error
Stops
A parameter error was detected in the
MEWNET-W2 configuration area. Set a
correct parameter.
A A
E30
Interrupt
error 0
Stops
Probably a hardware abnormality.
Please contact your dealer.
E31
Interrupt
error 1
Stops
An interrupt occurred without an interrupt
request . A hardware problem or error due to
noise is possible.
Turn off the power and check the noise
conditions.
A A A A A A A A A
E32
Interrupt
error 2
Stops
There is no interrupt program for an interrupt
which occurred.
Check the number of the interrupt program
and change it to agree with the interrupt
request..
A A A A A A A A A
E33
Multi-CPU
data
unmatch
error
CPU2
Stops
This error occurs when a FP3 / FP10SH is
used as CPU2 for a multi-CPU system.
Refer to Multi-CPU system Manual”.
A A
E34
I/O status
error
Stops
An abnormal unit is installed.
-FPΣ, FP0R(FP0R mode), FP-X, FP2,
FP2SH and FP10SH:
Check the contents of special data register
DT90036 and locate the abnormal unit. Then
turn off the power and replace the unit with a
new one.
-FP3:
Check the contents of special data register
DT9036 and locate the abnormal unit. Then
turn off the power and replace the unit with a
new one.
A A
A
A A A
E35
MEWNET-F
slave illegal
unit error
Stops
A unit, which cannot be installed on the slave
station of the MEWNET-F link system, is
installed on the slave station.
Remove the illegal unit from the slave
station.
A A A
E36
MEWNET-F
(remote I/O)
limitation
error
Stops
The number of slots or I/O points used for
MEWNET-F(remote I/O) system exceeds the
limitation.
Re-configure the system so that the
number of slots and I/O points is within the
specified range.
A A A
E37
MEWNET-F
I/O mapping
error
Stops
I/O overlap or I/O setting that is over the
range is detected in the allocated I/O and
MEWNET-F I/O map.
Re-configure the I/O map correctly
A A A
A: Available