EasyManua.ls Logo

Panasonic GHP - Setting Terminator Status

Panasonic GHP
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
10.0.
Setting Terminator Status
The terminating resistance of the indoor/outdoor operation lines should have 1 location set to “with resistance” [SHORT]
if there is 1 refrigerant system. If there are 2 or more refrigerant systems, set 2 locations to “with resistance” [SHORT]. If
2 locations are set to “with resistance”, set the 2 terminating resistances for the outdoor unit nearest to the central control
device, and for the one furthest away, to “with resistance” [SHORT], and all other outdoor units to “without resistance”
[OPEN]. This is to stabilize communications. Setting 3 or more locations to “with resistance” is prohibited.
If the terminating resistance of an outdoor unit for a multi-system of U-20GES3E5 and U-10MES2E8 is set to “with
resistance” [SHORT], set the outdoor unit of the gas heat pump air conditioner to “with resistance” [SHORT], and set the
outdoor unit of the U-10MES2E8 to “without resistance” [OPEN].
Outdoor unit
U-20GES3E5
Outdoor unit
U-20GES3E5
Outdoor unit
U-10MES2E8
Outdoor unit
U-10MES2E8
Outdoor unit
Terminating resistance [SHORT]
Terminating resistance [SHORT]
Terminating resistance [OPEN]
Terminating resistance [OPEN]
Terminating resistance [OPEN]
Refrigerant system 1
Refrigerant system 2
Refrigerant system Z
Central control
device
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 5
The terminating resistance for the gas heat pump air conditioner is set using DIP switch SW010 on the outdoor main circuit
board.
The terminating resistance for the U-10MES2E8 is set by switching the shorted socket of the terminating resistance pin
(3P) (CN67) of the outdoor unit control board.
[SHORT]
(at shipment)
SHORT / OPEN
The terminating resistance pin (3P) (CN67)
[OPEN]
SHORT / OPEN
Fig. 6