Outdoor unit
DOWN UP
P Oil error time Hr

10 Set engine rpm min
-1

600 to 2200
11 Engine rpm min
-1

600 to 2200
12 Compressor inlet pressure MPa

0.60 to 0.90 0.30 to 1.10
13 Compressor outlet pressure MPa

2.30 to 3.20 2.40 to 3.30
14 Compressor inlet temperature °C

5 to 30 0 to 30
15 Compressor outlet temperature °C

70 to 110 80 to 110
16
Outdoor heat exchanger 1 inlet
temperature
°C

30 to 50 -5 to 10
20 Coolant temperature °C

60 to 83 55 to 83
21 Outside air temperature °C

22 Clutch 1 coil temperature °C

24 Hot water outlet temperature °C

26
Oil level measurement
temperature
°C

31 Clutch 2 coil temperature °C

30 to 90 30 to 90
34 Exhaust gas temperature °C

45 to 90 40 to 80
38 Outdoor fan 1 %

0 to 108 0 to 90
39 Outdoor fan 2 %

0 to 108 0 to 90
41 Outdoor fan 1 revolutions min
-1

0 to 700 0 to 580
42 Outdoor fan 2 revolutions min
-1

0 to 700 0 to 580
44 Set coolant pump min
-1

3700 3700
45 Coolant pump revolutions min
-1

3700 3700
46 Throttle Step

47 Fuel gas adjustment valve Step

48 Liquid valve Step

0 to 100 0 to 480
49 Bypass valve Step

20 20
50 Outdoor electric valve 1 Step

480 0 to 480
51 Outdoor electric valve 2 Step

480 0 to 480
52 Coolant 3-way valve Step

50 50 to 1950
53 Electric cooler valve Step

50 to 1950 50 to 1950
54 Hot water discharge 3-way valve Step

50 to 1950 50 to 1950
55
Rotation speed variation value
(F_r pm)

59 Engine load ratio

0 to 6 0 to 6
60 Engine ignition timing Degrees

8 to 40 8 to 40
61 Cylinder number when ameout

15