Standard: ∞
Measure resistance between the ground screw and terminal board 1.
Measure resistance between the ground screw and terminal board 2.
Standard: ∞
If there is resistance, a sensor ground fault has occurred.
Ground
Outdoor unit
(Indoor unit)
Sensor
Sensor ground fault check (* Sensor ground faults will also result in communication faults.)
· Sensor type (thermistor) ground fault check (turn off power for units)
For each of the indoor/outdoor units connected by the operation cable, measure the
resistance between the sensor wiring and ground screw for both of the sensor wires
and ground screws.
Outdoor unit
Indoor unit 1
Ground
Ground Ground Ground
Ground
Remote controller
Indoor unit 2 Indoor unit 3 Indoor unit 4
Indoor/outdoor control wire
Ground Ground Ground
Remote controller
Outdoor unit
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
Ground
Ground
Indoor/outdoor control wire
Outdoor unit
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
Ground
Ground
Remote controller
Ground Ground Ground
Indoor/outdoor control wire
Ground fault check
Measure resistance between the ground
screw and terminal board 1.
Measure resistance between the ground
screw and terminal board 2.
Standard:∞
Wire break or disconnection check
Measure resistance on the termi-
nal board of each unit.
Short circuit check
Measure resistance between terminal
board 1 and terminal board 2.
Standard:Approx.75to100Ω(with
one terminal resistor present)
Example: A wire break or disconnection occurs at x (with one outdoor unit terminal resistor
present).
The resistance value for
,
, and
isapprox.75to100Ω.
The resistance value for
and
is∞.
* If the resistance for
is∞,checktheterminalresistorfortheoutdoormain
board, and check wiring between the outdoor main board and the outdoor unit
terminal board.