General-purpose
memory shortage
General-purpose memory shortage in the destination PLC.
The PLC (FP2/FP2SH) is set to the RUN mode. Change to the
REMOTE mode or PROG. mode.
Check if a device that cannot be forcibly operated in the PROG.
mode has been forcibly turned on or off.
The record area for
logging was
overwritten.
A SD memory card is not inserted.
Check the SD memory card slot.
Data cannot be written into the SD memory card. Check whether
the SD memory card is not write-protected.
As the memory of the SD memory card has been exhausted.
Delete some data in the SD memory card or prepare a new SD
memory card.
The setting to stop writing to SD memory card has been set.
Cancel the writing stop setting.
SD memory card
writing error
The setting to stop writing to SD memory card has been set.
Cancel the writing stop setting.
The record area for
logging cannot be
reserved in the
SRAM.
The firmware file loaded from a SD card is damaged.
Recreate the file in the SD card.
Ethernet IP address
setting error
The IP address for Ethernet is not specified correctly. Check the
IP address for the GT.
Ethernet subnet mask
setting error
The subnet mask for Ethernet is not specified correctly. Check
the subnet mask for the GT.
Ethernet default
gateway setting error
The default gateway for Ethernet is not specified correctly.
Check the default gateway for the GT.
Ethernet port number
setting error
The port number for Ethernet is not specified correctly. Check
the port number error for the GT.
Index register value
error
The device value for index modifier is out of the setting range.
Check the setting value.
Start time device
value error
The value at the start of the line graph function is out of the
setting range. Check the setting value.
Connected GT
designation area error
The bit corresponding
to the connected GT
in the connected GT
designation area.
The bit in the connected GT designation area corresponding to
the station number of the connected GT is not on.
Check the connected GT designation area.